Voltage Gradient Across High Voltage Cable Insulation
Core insulation may be coloured red, yellow, blue and black to identify the
three phases and neutral. Twin cores are coloured red and black. Singlecore
cables are identified by coloured PVC tape applied to the outer
sheath.
2.4 Cable Stress Relief
The copper screen is often terminated in a 'stress cone', which may be
seen in Figure 7. This is to spread the electric stress which would
otherwise tend to concentrate where the screen is cut off at a cable end
and could lead to breakdown. This is further discussed in para. 6.4
2.5 Bedding
The bedding consists of a layer of PVC extruded over the core insulation
as a base for the armouring.
2.6 Armouring
Mechanical protection of the cable is provided by a single layer of wire
strands laid over the bedding. Steel wire is used for 3-core or 4-core
cables, but single-core cables have aluminium wire armouring. With 3-core
or 4-core cables the vector sum of the currents in the conductors is
zero, and there is virtually no resultant magnetic flux. This is not so
however for a single-core cable, where eddy-current heating would occur
if a magnetic material were used for the armouring. Armouring is
described as Steel Wire Armoured (SWA) or Aluminium Wire Armoured
(AWA).
Outer Sheath
The outer sheath of extruded PVC protects the armouring and the cable
against moisture and generally provides an overall protective covering.
High-voltage cables are identified by outer sheaths coloured red; a black
sheath indicates a low-voltage cable (see also para. 7)
2.8 Selection of Power Cables
The following considerations are taken into account when selecting a
power cable for a particular application:
(a) The System Voltage and Method of Earthing
A low-voltage system usually has a solidly earthed neutral so
that the line-to-earth voltage cannot rise higher than (line
volts) ÷ ? 3. However, cables for low-voltage use are
insulated for 600V rms score to earth and 1000V rms core
to core.
High-voltage cables used in Shell installations are rated
1900/3300V or 3810/6600V or 6600/11000V, phase/line. In
selecting the voltage grade of cable, the highest voltage to
earth must be allowed for. For example, on a normal 6.6kV
unearthed system, a line conductor can achieve almost 6.6kV
to earth under earth-fault conditions, To withstand this, a
cable insulated for 6600/11000V must therefore be used.
(b) The Normal Current of the Cable
The conductors within a cable have resistance, and
therefore /2 R heating occurs when currents pass through
them, The maximum permissible temperature of the cable
depends upon the material of the insulation, and a conductor
size must be chosen so that this temperature is not
exceeded. Tables giving the continuous current-carrying
capacities of different cables are given in manufacturers'
literature and in the Regulations for the Electrical
Equipment of Buildings published by the Institution of
Electrical Engineers.